IS 5820: Precast Concrete Cable Covers

IS 5820:1970
Cable Covers
1970

Key technical information and requirements related to Cable Covers from IS 5820:1970.

Cable Covers Utilities IS 5820:1970 Precast Concrete Cable Covers
IS 5820: 1970 SPECIFICATION FOR PRECAST CONCRETE CABLE COVERS
Key Information
CLASSIFICATION
Class Description of Cable Cover Conditions Where Normally Used
EHV Reinforced precast concrete, with peak For underground power cables of voltage rating 22kV and 33kV
HVP Unreinforced precast concrete, with peak For power cables of voltage rating above 1.1 kV excluding 22 kV and above
HV Unreinforced precast concrete, flat For power cables up to and including 1.1 kV
LV Unreinforced precast concrete, flat For power cables up to and including 1.1 kV
DIMENSIONS & MINIMUM AVERAGE BREAKING LOAD
# Class Type No. Shape Dimensions (mm) Dimensions (mm) Dimensions (mm) Dimensions (mm) Min. Avg. Breaking Load for Unreinforced Covers kg
# Class Type No. Shape L W T T’
(Peak)
Min. Avg. Breaking Load for Unreinforced Covers kg
1 EHV 1 With peak 450 230 50 75 450
2 With peak 600 230 50 75 750
2 HVP 1 With peak 300 180 40 65 300
2 With peak 450 180 40 65 350
3 HV 1 Flat 300 180 40 - 300
2 Flat 450 180 40 - 350
4 LV 1 Flat 250 150 40 - 200
2 Flat 300 180 40 - 200
3 Flat 450 180 40 - 200
TOLERANCES
Length & Width: +/- 3mm
Thickness: +/- 2mm.
SAMPLING
12 Samples at random for every consignment of 2,000 cable covers or less, and a further 12 samples for every further 12,000 cable covers or part of 12,000 covers.
(For further details please refer to the Standard)